An inspection robot is most useful when this round’s readings can be compared with the same readings from the last round. Most of that is decided when the route is planned: where the robot stops, where the camera points, how long it waits and what it stores. Here is a method, with MINI 640-2 Radiometric as the example. Figures marked calculated are worked out, not measured.

Start from the equipment list, not the map

List every item the robot must check (a breaker, a cable termination, a motor bearing, a transformer, a gauge), the part of it that matters, its normal temperature, and the smallest detail you need to resolve. Each item gets a viewpoint. The route is what joins the viewpoints.

Choose each viewpoint

  • Distance. Two limits apply: pixels on the target and the lens’s sharp range. With at least 3 × 3 pixels on the target, the farthest distance is target size ÷ (3 × IFOV). With the 9.1 mm lens (1.3 mrad) that is about 1.5 m for a 6 mm fuse terminal, and about 6.4 m for a 25 mm bearing cap (calculated). But this lens is sharp from 1.2 to 5.5 m on MINI 640-2 Radiometric, so the bearing cap’s viewpoint has to be within 5.5 m, and the terminal’s between 1.2 and 1.5 m.
  • Safety. Plan every viewpoint outside the site’s minimum approach distance to live parts. Never remove guards or open live enclosures to get a clear view; where a panel must be seen inside, use infrared inspection windows fitted for the purpose.
  • Angle. Look at the surface within about 45° of perpendicular. At steeper angles paints and plastics read low, and readings on metal change with angle. On shiny surfaces, stay a few degrees off square-on so that the robot’s own reflection is not on the target.
  • Reflections and background. Avoid viewpoints where a lamp, a sunlit window or a hot pipe reflects in the target, and where something hot sits right behind a small target.
  • Line of sight. Ordinary glass and clear plastic viewing panels block the 8–14 μm band. A mesh guard or a cable in front of the target mixes its own temperature into the reading.

Stop, settle, measure

Measure from standstill. After the robot stops, wait for the mast or arm to stop swaying. The detector itself settles fast: with a thermal time constant under 12 ms on this core, five time constants (about 99%) take at most 60 ms, about two frames at 30 Hz (calculated). Processing and transfer add some delay, so discard the first few frames after the camera is still. Then take a short burst, for example 10 frames (a third of a second), and use the median or average of each region.

Uncooled cores correct their non-uniformity from time to time; this core supports both shutter and shutterless correction, and with a shutter the image freezes briefly while it happens. Check whether the timing of the correction can be controlled in your setup and whether frames show when it happened. If it can, run it between viewpoints; either way, discard frames captured during or just after a correction.

The same view every round

At inspection distances a small pose error moves the target a long way in the image. With the 9.1 mm lens, a 1° pointing error moves the image by about 13 pixels at any distance, and at 2 m a 5 cm sideways error moves it by about 19 pixels (calculated). Regions fixed in pixel coordinates will miss their targets. Use the robot’s localisation plus a fixed pan-tilt preset for each viewpoint, then align each frame to a reference image of that viewpoint, or place regions relative to features you can find in the image, before you read temperatures.

Readings that mean something

  • Correct each region for its own emissivity and reflected temperature. If the core’s setting applies to the whole frame, do this per region in your software. Painted surfaces and insulation read well; bare metal needs a patch of high-emissivity tape or paint, fitted while the equipment is de-energised.
  • Store the conditions with each reading: time, ambient temperature and, for electrical equipment, the load. Heating power goes with the square of the current, and the temperature rise roughly so.
  • Compare like with like: one phase against the other two, a motor against an identical motor, this round against the same time last week.
  • Alarm on two things: an absolute limit for safety, and a rise against the item’s own history.

Looking after the core on a moving robot

  • Ambient. Measurement on MINI 640-2 Radiometric is specified for −10°C to +70°C ambient, meaning the air around the core inside its housing. When the robot moves between very different temperatures, such as outdoors to indoors, readings need time to settle; measure how long in your own tests and plan the route around it. A freezer below −10°C is outside the measuring range unless the core sits in a heated housing.
  • Heat sources. Mount the core away from the robot’s motor drivers, computer and battery, and out of their exhaust air. A core that warms unevenly drifts.
  • Vibration. The maker’s test levels for this core are 6.06 g random vibration on all axes and 80 g, 4 ms terminal-peak sawtooth shocks on three axes in both directions. Ask for the full test profile, compare it with what you measure at the mounting point, and check readings on your own robot while it drives.
  • Window. Include the window’s transmission in the temperature correction and check readings through the window. Dirt on it absorbs part of the signal and pulls readings toward the window’s own temperature, and moving from cold into warm, humid air can fog it; water blocks this band. Include cleaning in maintenance.

What to store at each viewpoint

Region statistics (maximum, minimum, average) every round; a full temperature frame when an alarm triggers, or every so often for reference; and an image a person can look at. A full frame of 640 × 512 values at two bytes per pixel is about 0.66 MB, so one full frame at each of 100 viewpoints is about 66 MB per round (calculated).

Checklist

  1. Equipment list, with the part that matters and its smallest detail
  2. Viewpoint distance from pixels on target and the lens’s sharp range, outside approach distances
  3. Viewing angle, reflections and line of sight at each viewpoint
  4. Stop, settle and capture timing, with frames around corrections discarded
  5. Repeatable pose, and image alignment before reading regions
  6. Emissivity and reflected temperature per region, conditions stored, comparisons and alarms
  7. Core ambient, heat sources, vibration and window care

MINI 640-2 Radiometric is a 21 × 21 mm module supplied with its lens; the robot, housing, window and inspection software are the robot builder’s. On the USB version, temperature readout and control go through TSDK, our SDK for this module, with builds for Linux (Ubuntu, Raspberry Pi and Jetson); it has been tested on our modules, comes at no extra charge and is provided after payment.